Why did whole-house ac stop working, still blowing but not cold?

The air conditioning worked fine then suddenly yesterday it stopped being cold, but fan still works.

답변되었습니다! View the answer 저도 같은 문제를 겪고 있습니다

좋은 질문 입니까?

점수 2

댓글:

@jlozier when you say the fan works you are talking about the outside unit? Can you hear your compressor kick in? When you touch the lines coming out of the cormpressor, are they cold/cool/hot? What make and model is your AC?

의 답변

If this is a home refrigerated air unit, go outside and look at the pipes going into the exchange unit and see if they are frosted over or even have ice on them. Is that fan running?

의 답변

Here is more information, thanks for comments.

While copying the numbers, the unit attempted to start, twice, but went off in a second or two.

I think this indicates that the thermostat is calling for AC but the compressor can/t doesn't deliver.

Is a freon recharge in order? This is something I've never done, but there are access caps on the pipes that go into the house.

The unit is Lennox M/N H529-024-5P, S/N 5805J11611.

의 답변

@jlozier you said " the unit attempted to start, twice, but went off in a second or two." Does it no longer come on? Does the main fan turn? Right now it does not sound like Freon issues at all. Sounds more like the start capacitors etc. You got a multimeter? BTW those things pack a punch, so you want to be careful around the electrical connectors etc. check your model number once more. Is it possible that yours is a Hs29-024 instead of H529? Post some images of your wiring and the capacitors (large round cannisters:-) with your question. There are multiple ways this may have been wired up. Don't touch anything and consider turning the breaker off. Remember that capacitors hold a charge long after you turn the power off, so do not touch anything,yet. Use this guide Adding images to an existing question for that.

의 답변

You need to take a amp draw to see if the compressor is trying to start. It might be drawing locked rotor and kicking off on the thermal overload.

의 답변

의견 추가하세요
Fixmas/픽스마스 분위기를 띄우세요
FIXMAS12 코드로 $50 이상 구매시 $12 할인을 받으십시오
Fixmas/픽스마스 분위기를 띄우세요
FIXMAS12 코드로 $50 이상 구매시 $12 할인을 받으십시오

3개의 답변

선택된 해법

@jlozier since this sounds more like a power issue, I would suggest that you check the power to your AC unit first. It should be 240V (depending where in the world you are:-) If you have power to the AC then you want to check the run capacitor. It is in charge of the fan motor and the compressor. Check it for bulging, leaking and/or severe corrosion. If so replace it. The next part on my checklist is the contactor. That is basically a 24V relay that closes the circuit when your thermostat calls for cooling. There are a few different ones for your AC model, which makes it somewhat important that you post some pictures with your question. Use this guide for that since it will allow us to see what you see. Please remember that the voltage and amperage on your AC packs a heavy punch. Do not touch any live wires etc.

BTW you and I will not beable to purchase any refrigerant since that requires a HVAC license and some nifty gauges to refill the unit.

Block Image

해당 답변은 도움이 되었습니까?

점수 2

댓글:

Thanks, oldturkey and others, this is beyond me, I'm going to call a professional.

의 답변

의견 추가하세요

It's easy , the freon is in really low value.

https://simple.wikipedia.org/wiki/Freon

Just replace it by adding more "gas".

해당 답변은 도움이 되었습니까?

점수 0
의견 추가하세요

Mine does that, occasionally, after a power outage and needs to be reset. There are instructions to do that but I hate electricity so my neighbor had me turn it off at the thermostat, then he unplugged it (at the outside power coupling), we talked a few minutes, then he plugged it back in and I turned it back on and all was well.

해당 답변은 도움이 되었습니까?

점수 0
의견 추가하세요